How to size a solar array for off-grid: step-by-step
From daily kWh to panel count, battery days and generator hours, with every number in the worked example labelled as an example.
On this page
- Step 1: daily energy, including the inverter’s own appetite
- Step 2: find the worst month, and its output per kilowatt
- Step 3: add the losses PVWatts does not know about
- Step 4: array size and panel count
- Step 5: battery for the no-sun days, then recharge
- Step 6: the generator as backup
- Step 7: check the inverter can take the array
- How sensitive is the answer?
- The whole example on one page
- Common mistakes
- Next
Most off-grid sizing mistakes come from stopping one step early: an array that covers the daily load but cannot refill the battery, or one sized in July for a house that is short in December. This guide builds a complete answer in order, using one example throughout. Every load, panel and sun figure in the example is made up to show the method. The EG4 numbers (efficiencies, battery energy, inverter limits) are from the maker’s sheets. For your own numbers, use solar by ZIP and the system finder.

Step 1: daily energy, including the inverter’s own appetite
Energy is power over time: a kilowatt-hour is one kilowatt for one hour. List each load in watts and hours, as in how much battery do you need, and total it. For the example, say the loads add up to 12 kWh per day.
Then add the inverter. The 12000XP lists idle consumption under 70 W, and 70 W for 24 hours is 70 × 24 ÷ 1,000 = 1.68 kWh. Our arithmetic: 12 + 1.68 = 13.68 kWh per day. (See how to read an inverter datasheet for the conditions on that figure.)
Step 2: find the worst month, and its output per kilowatt
Penn State’s stand-alone sizing lesson says such a system should supply loads in any month, and that the month with the highest design ratio, lowest insolation against highest load, is the critical design month. Get the numbers from PVWatts, a tool for estimating the energy production of a grid-connected PV system, which reports monthly and annual totals. Enter your address and a 1 kW system, and read the lowest month.
Peak sun hours are the shorthand. The University of Arizona Cooperative Extension says a location with 3.5 peak sun hours reaches 1,000 W/m² for 3.5 hours per day. That is a measure of energy, not of how long the sun is up. PVWatts already includes a default total system loss of 14% (soiling, shading, mismatch, wiring, connections and more).
For the example, suppose PVWatts shows 2.4 kWh per day from each kW of panels in the worst month. That is invented, though it is what 3.0 peak sun hours would give at about 80% overall efficiency (3.0 × 0.80 = 2.4, our assumption). Your own figure will differ, and for a sunny region may be much higher.
Step 3: add the losses PVWatts does not know about
PVWatts models the array and an inverter. It does not know that your system stores energy and then converts it again. Penn State’s off-grid array formula includes the battery’s efficiency for this reason. For EG4 gear, take the figures from the sheets: the 314Ah battery lists 95% round-trip efficiency, and the 12000XP lists 90.2% maximum efficiency from battery to loads. Both are maxima.
Assume (our assumption) that half the daily energy is used straight from the panels and half goes through the battery. Energy that goes through the battery takes 1 ÷ (0.95 × 0.902) = 1.167 kWh of generation per kWh used (our arithmetic). So the generation needed is:
Step 4: array size and panel count
14.82 ÷ 2.4 = 6.18 kW. With 400 W panels (an assumed size), 6.18 ÷ 0.4 = 15.4, so 16 panels, 6.4 kW.
Now stress it. The PVWatts manual says its errors may be as high as ±10% for annual totals and ±30% for monthly totals against typical weather, and an actual year can deviate by up to ±20% annually and ±40% monthly. If the worst month comes in 30% low, output per kW is 2.4 × 0.7 = 1.68 kWh, and the array needed is 14.82 ÷ 1.68 = 8.8 kW, which is 23 panels. That gap between 16 and 23 panels is the cost of being wrong about one month.

Step 5: battery for the no-sun days, then recharge
Decide how many days the battery alone must carry the house. Penn State calls this autonomy, and ties the days you need to your peak sun hours and the availability you want. For the example, two days.
- Battery energy out per day: 13.68 kWh ÷ 0.902 = 15.17 kWh (our arithmetic, treating all energy as coming through the battery-to-loads path).
- Two days: 2 × 15.17 = 30.3 kWh.
- The 314Ah battery lists 12.86 kWh of usable energy (80% recommended depth of discharge). 30.3 ÷ 12.86 = 2.36, so three batteries, about 38.6 kWh usable. Three batteries are 942 Ah, above the 12000XP’s recommended minimum of more than 400 Ah.
So far the plan looks complete. Now ask the question most plans skip: how long does the battery take to refill? After two sunless days it is down about 30.3 kWh. To put that back at 95% round-trip efficiency takes about 30.3 ÷ 0.95 = 31.9 kWh of generation (our simplification). The refill rate is what the array makes in a day minus what the house uses that day. Here is the example at three array sizes, on an average worst-month day (2.4 kWh per kW):
| Panels (400 W) | Array | Output per day | Surplus after the 14.82 kWh need | Days to refill 31.9 kWh |
|---|---|---|---|---|
| 16 | 6.4 kW | 15.4 kWh | 0.5 kWh | about 59 |
| 24 | 9.6 kW | 23.0 kWh | 8.2 kWh | about 3.9 |
| 32 | 12.8 kW | 30.7 kWh | 15.9 kWh | about 2.0 |
The array that “covers the load” never refills the battery in winter. Recharge time, not the daily load, is what pushes the array up. The same arrays produce far more than the house needs in summer, when the extra output has nowhere useful to go once the battery is full.
Step 6: the generator as backup
A generator turns the long-recharge problem into hours of run time. The 12000XP sheet lists a recommended generator capacity of 6,000 to 15,000 W. A separate AC charger can also do the job: the Chargeverter GC lists a maximum output of 5,120 W at 240 VAC. Our arithmetic for the example: 31.9 kWh ÷ 5.12 kW is about 6.2 hours to refill the battery at the charger’s maximum, ignoring other losses and any charge-rate limits.
That gives a decision rule. Pick the array for the recharge days you can accept in your worst month, then use the generator for sequences of bad weather longer than your battery days. The 6.4 kW array in the table would need a generator for nearly every refill. The 9.6 kW array refills in about four days, so a generator only covers unusual weather.
Step 7: check the inverter can take the array
Every inverter lists a recommended maximum solar input and a current limit per MPPT. These come from the sheets:
| Inverter | MPPTs and usable current | Recommended maximum solar input | Output on battery |
|---|---|---|---|
| 6000XP | 2 × 17 A | 10,000 W | 6,000 W |
| 12000XP | 2 × 35 A | 28,000 W (14,000 W per MPPT); 24,000 W maximum utilized | 12,000 W without PV; 15,000 W with PV on model IV-15000 |
| 18kPV | 25 A, 15 A, 15 A | 21,000 W; 18,000 W maximum utilized | 12,000 W rated |
| FlexBOSS21 | 26 A, 26 A, 15 A (rated) | 21 kW | 12 kW battery only; 16 kW with PV and grid |
Apply the example. The 12.8 kW array fits the 12000XP, 18kPV and FlexBOSS21 solar limits and exceeds the 6000XP’s 10,000 W. Even the 9.6 kW array fits the 6000XP’s solar limit, but the 6000XP’s 6,000 W output has to carry your biggest simultaneous load, and its recommended battery capacity is more than 200 Ah. Next check strings. The Voc rises in the cold, so run the cold-weather voltage check in the string calculator and read cold weather and solar. Split the panels across MPPTs as the sheet’s current limits allow and compare each string’s short-circuit current with the MPPT’s short-circuit rating on the sheet (44 A per MPPT on the 12000XP). Wiring, protection and the interconnection are electrical work: they need a licensed electrician and local code.
If your largest loads include a well pump or an air conditioner, check surge capability before you pick the inverter: why a well pump trips your inverter. For a model-by-model comparison, see EG4 inverters compared.

How sensitive is the answer?
Three inputs move the result most, and you can test them with the same arithmetic.
- When the energy is used. If all 13.68 kWh went through the battery, generation needed is 13.68 × 1.167 = 15.96 kWh a day, an array of 15.96 ÷ 2.4 = 6.65 kW, or 17 panels. If all of it ran straight from the panels, it is 13.68 ÷ 2.4 = 5.70 kW, or 15 panels. Moving laundry and pumping to the sunny hours saves panels.
- The load itself. At the 50/50 split, each kWh a day you remove saves 1.083 kWh of generation, which is 1.083 ÷ 2.4 = 0.45 kW, about one panel. A cheaper way to shrink the array is often a more efficient appliance, not another panel.
- The worst-month figure. It sits in the denominator, so a 30% error moves the array from 16 to 23 panels, as step 4 shows. This is the number to take from PVWatts for your own address and not from this page.
The example leaves out several smaller things: wiring losses between the array and the inverter beyond the 14% default, the battery’s state-of-charge floor, the temperature derating of the battery, and any change in your loads from season to season. They matter less than the three above, but they all point the same way: toward a bigger array or a longer generator run.
The whole example on one page
| Step | Result | Source of the number |
|---|---|---|
| Daily loads | 12 kWh | Example |
| Plus inverter idle (70 W × 24 h) | 13.68 kWh | 12000XP sheet |
| Plus battery losses (half through the battery) | 14.82 kWh of generation per day | Sheets and our assumption |
| Worst-month output | 2.4 kWh per kW per day | Example, to be replaced with PVWatts |
| Array | 6.2 kW minimum; 16 panels of 400 W | Our arithmetic |
| Battery for two sunless days | 30.3 kWh, three 314Ah batteries | Sheet and our arithmetic |
| Array chosen for refill | 24 panels (9.6 kW), about 4 days to refill | Our arithmetic |
| Backup | about 6 hours of generator charging at 5.12 kW | Charger sheet and our arithmetic |
Common mistakes
- Sizing from an annual average. The worst month decides.
- Forgetting the inverter’s idle draw. It is 1.68 kWh a day at 70 W.
- Stopping at the battery. If the array cannot refill the battery, the days of autonomy are used once and not replaced.
- Using the default snow and soiling inputs. PVWatts’ default total loss is 14% with snow at zero. Adjust it for your site, or add margin as in step 4.
- Counting the maximum efficiencies as typical. They are the best case on each path.
- Ignoring the inverter’s limits. Check solar input, MPPT current and output on battery before ordering panels.
Next
Put your own numbers into solar by ZIP for the worst month, then let the system finder narrow the hardware. If you are not sure off-grid is the right design, read off-grid, hybrid or grid-tied, and when you are ready to buy, buying solar equipment online.
Questions people ask
How many solar panels do I need to go off-grid?
Divide your daily energy need, including losses, by the kWh that one kilowatt of panels produces on an average day in your worst month, then divide the result in kW by your panel’s watts. The number depends on your loads and location, so use your own figures in a tool such as PVWatts.
What are peak sun hours?
The University of Arizona Cooperative Extension describes peak sun hours as the number of hours per day that sunlight intensity reaches 1,000 W/m². A place with 3.5 peak sun hours gets as much energy as 3.5 hours at that intensity, not 3.5 hours of daylight.
Why size for the worst month instead of the average?
Because a stand-alone system has to supply the loads in every month. If the array is sized to an average, the lowest-sun month leaves you short, when a generator or a dark house costs the most.
Do I need a generator with an off-grid solar system?
A generator can cover a long run of poor weather instead of sizing the array and battery for it. In the worked example, refilling a drained battery takes about 6 hours of charging at 5.12 kW. Whether you need one depends on the recharge time you can accept.
How much should the array exceed the daily load?
Enough that the surplus in your worst month refills the battery in an acceptable number of days. An array that only matches the daily load has almost no surplus to recharge with.
Can the inverter take the whole array?
Check each inverter’s maximum recommended solar input and the current limit of each MPPT. For example, the EG4 6000XP lists 10,000 W and the 12000XP 28,000 W, with 24,000 W maximum utilized.